Section 890.APPENDIX A
Plumbing Materials, Equipment, Use Restrictions and Applicable Standards
Section 890.TABLE B Minimum
Number of Plumbing Fixtures
|
Type of Building
|
|
All Facilities for Employee Use
|
Single Dwelling or Unit of Multiple Dwelling; Condo. or
Apartment; or Hotel/Motel Unit
|
|
|
|
|
Male
|
Female
|
|
|
|
|
Water closets
(Fixtures per person)
|
For 1-5 Total Employees See
Section 890.810(b)(1)
|
1 per dwelling or unit
|
|
|
|
|
|
1:
|
1-15
|
1:
|
1-15
|
|
|
|
|
2:
|
16-35
|
2:
|
16-35
|
|
|
|
|
3:
|
36-55
|
3:
|
36-55
|
|
|
|
|
4:
|
56-80
|
4:
|
56-80
|
|
|
|
|
5:
|
81-110
|
5:
|
81-110
|
|
|
|
|
Over 110, add 1 fixture per
restroom for each additional 40 males/females.
|
|
|
|
|
|
|
(See Footnote #1)
|
|
|
|
|
Urinals
|
See footnote #2
|
See footnote #2
|
None
|
|
|
|
Lavatories3
|
1:
|
1-15
|
1:
|
1-15
|
|
1 per dwelling or unit
|
|
(Fixtures per person)
|
2:
|
16-35
|
2:
|
16-35
|
|
|
|
|
3:
|
36-60
|
3:
|
36-60
|
|
|
|
|
Over 60, add 1 fixture per
restroom for each additional 45 males/females.
|
|
|
|
|
Bathtubs/Showers
|
1 per 107
|
1 per 107
|
1 per dwelling or unit
|
|
|
(If Required)
|
|
|
|
|
|
Drinking fountains4
|
1
per 75
|
None
|
|
(Fixtures per person)
|
|
|
|
|
Other Fixtures5
|
None
|
1 Double Kitchen Sink; or 1
Single Bowl − 24" x 21" x 6˝" minimum
1 Laundry Tray or 1 Automatic
Laundry Washing Machine connection for each 4 units5
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Back to the
TOP
Type of Building
|
Dormitories
|
Assembly
Places: Sports Arenas, Stadiums, Convention Halls, Etc.
|
|
|
|
|
Male
|
Female
|
Male
|
Female
|
|
|
|
Water Closet (Fixtures per
person)
|
1 per 10
|
1 per 8
|
1:
|
1-100
|
2:
|
1-100
|
|
Add 1 fixture for each
additional 25 males over 10; and 1 for each additional 20 females over 8.
|
2:
|
101-200
|
3:
|
101-150
|
|
3:
|
201-400
|
4:
|
151-200
|
|
4:
|
400-800
|
5:
|
201-300
|
|
|
|
6:
|
301-400
|
|
|
|
7:
|
401-500
|
|
|
|
8:
|
501-650
|
|
|
|
9:
|
651-800
|
|
|
Over 800, add 1 fixture for
each additional 700 males and 1 for each 200 females.
See Footnote #1
|
|
|
|
Urinals
|
1 per 25
|
See
Footnote #2
|
1:
|
1-100
|
See
Footnote #2
|
|
(Fixtures per person)
|
Over 150, add 1 fixture for
each 50 males added; over 400, add 1 for each 200 males added.2
|
2:
|
101-200
|
|
3:
|
201-400
|
|
4:
|
401-600
|
|
Over 600, add 1 fixture for
each additional 250 persons.
|
|
|
|
|
|
|
Lavatories3
|
1 per 12
|
1 per 12
|
1:
|
1-200
|
1:
|
1-200
|
|
(Fixtures per person)
|
Over 12, add 1 fixture for
each additional 20 males and 1 for each 15 females.
|
2:
|
201-400
|
2:
|
201-400
|
|
3:
|
401-750
|
3:
|
401-750
|
|
|
|
|
Over 750,
add 1 fixture per restroom for each added 400 males/females.
|
|
|
|
Bathtubs, Showers
|
1
per 8
|
None
|
|
(Fixtures per person)
|
For females,
add 1 bathtub per 30; over 150, add 1 per 50.
|
|
|
|
|
|
|
|
|
|
|
Back to the
TOP
Type of Building
|
Dormitories
|
Assembly
Places: Sports Arenas, Stadiums, Convention Halls, Etc.
|
|
|
|
|
Male
|
Female
|
Male
|
Female
|
|
Drinking Fountains4
|
1
per 75
|
|
|
|
(Fixtures per person)
|
|
|
1 per each set of male and
female public restrooms
|
|
|
|
|
|
Other Fixtures
(Fixtures per person)
|
1
Service Sink per floor
|
1
Service Sink per floor
|
|
|
|
|
|
|
|
|
|
|
|
Back to the
TOP
Type of Building
|
Assembly
Places: Theaters, Auditoriums, Other Facilities for Spectator Events
|
Mercantile Units, Malls, Stores, Etc.
|
|
|
|
|
|
|
Male
|
Female
|
Male
|
Female
|
|
|
|
|
|
Water
Closet
(Fixtures
per person)
|
1:
|
1-100
|
2:
|
1-100
|
|
1:
|
1-100
|
1:
|
1-50
|
|
|
2:
|
101-200
|
3:
|
101-150
|
|
2:
|
101-200
|
2:
|
51-100
|
|
|
3:
|
201-400
|
4:
|
151-200
|
|
3:
|
201-400
|
3:
|
101-150
|
|
|
|
4:
|
401-800
|
5:
|
201-300
|
|
4:
|
401-800
|
4:
|
151-250
|
|
|
|
|
|
6:
|
301-400
|
|
|
|
5:
|
251-350
|
|
|
|
|
|
7:
|
401-500
|
|
|
|
6:
|
351-500
|
|
|
|
|
|
8:
|
501-650
|
|
|
|
7:
|
501-650
|
|
|
|
|
|
9:
|
651-800
|
|
|
8:
|
651-800
|
|
|
|
Over 800, add 1 fixture for
each additional 400 males and 1 for each 170 females.
See Footnote #1
|
Over 800,
add 1 fixture for each additional 500 males and 1 for each 175 females.
See
Footnote #1
|
|
|
|
|
|
|
|
Urinals
(Fixtures
per person)
|
1:
|
1-100
|
See Footnote #2
|
|
1:
|
51-200
|
See Footnote #2
|
|
|
2:
|
101-200
|
|
2:
|
201-400
|
|
|
3:
|
201-400
|
|
3:
|
401-600
|
|
|
|
4:
|
401-600
|
|
4:
|
601-800
|
|
|
|
Over 600, add 1 fixture for
each additional 300 males.
|
Over 800,
and 1 fixture for each additional 300.
|
|
|
|
|
|
Lavatories3
(Fixtures
per person)
|
1:
|
1-200
|
1:1-200
|
|
1:
|
1-200
|
1:
|
1-200
|
|
|
2:
|
201-400
|
2:201-400
|
|
2:
|
201-400
|
2:
|
201-400
|
|
|
3:
|
401-750
|
3:401-750
|
|
3:
|
401-750
|
3:
|
401-750
|
|
|
|
Over 750, add 1 fixture per
restroom for each added 400 males/females.
|
Over 750,
add 1 fixture per restroom for each added 350 males/females.
|
|
|
|
|
|
Drinking
Fountains4
(Fixtures
per person)
|
1:
|
1-100
|
|
|
|
1:
|
1-100
|
|
|
|
Over 100, add 1 for each
added500; over 1000, add 1 for each added 500; over 5000, add 1 for each
added 1000.
|
Over 100,
add 1 for each added 500; over 1000, add 1 for each added 500; over 5000, add
1 for each added 1000.
|
|
|
|
|
Other
Fixtures
(Fixtures
per person)
|
1
Service Sink per Floor
|
1
Service Sink per Floor
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Back to the
TOP
Type of Building
|
Worship
Places and
Funeral
Homes
|
Businesses Selling Motor Fuel
to the Public10
|
|
|
|
|
Male
|
Female
|
Male
|
Female
|
|
|
(See Footnote #1)
|
|
|
|
|
|
Water Closets
(Fixtures per person)
|
1 per 250
|
1 per 125
|
1 per
station
|
1 per
station
|
|
|
|
Urinals
(Fixtures per person)
|
1 per 250
|
See Footnote #2
|
None
|
|
|
|
Lavatories3
(Fixtures per person)
|
1 per 125
|
1 per 125
|
1 per
station
|
1 per
station
|
|
|
|
Other Fixtures
(Fixtures per person)
|
1 Service Sink
|
None
|
|
|
|
|
|
|
|
|
Back to the
TOP
Type of Building
|
Office Buildings/Public Buildings
|
Food Service Establishments, Pubs, Lounges, Nightclubs,
and Places Serving Food or Liquid to be Consumed on the Premises8
|
|
|
|
|
|
|
|
|
|
|
Male
|
Female
|
|
Male
|
Female
|
|
|
|
|
|
|
|
|
|
|
Water
Closet
(Fixtures
per person)
|
1:
|
1-15
|
1:
|
1-15
|
|
1:
|
1-100
|
1:
|
1-50
|
|
2:
|
16-35
|
2:
|
16-35
|
|
2:
|
101-300
|
2:
|
51-100
|
|
3:
|
36-55
|
3:
|
36-55
|
|
|
|
3:
|
101-150
|
|
|
4:
|
56-80
|
4:
|
56-80
|
|
|
|
4:
|
151-300
|
|
|
5:
|
81-110
|
5:
|
81-110
|
|
|
|
|
|
|
|
Over 110, add 1 fixture per restroom for each additional
40 males/females.
See Footnote #1
|
|
Over 300, add 1 fixture for each additional 200 males and
1 fixture per each 100 females. See Footnotes #1.
|
|
|
|
|
|
|
|
|
|
|
|
Urinals
(Fixtures per person)
|
See Footnote #2
|
|
1:
|
1-150
|
See
Footnote #2
|
|
|
|
|
|
|
Over 150, add 1 fixture for each added 150 males.
|
|
|
|
|
|
|
|
|
|
|
|
|
Lavatories3
(Fixtures
per person)
|
1:
|
1-15
|
1:
|
1-15
|
|
1:
|
1-100
|
1:
|
1-100
|
|
2:
|
16-35
|
2:
|
16-35
|
|
2:
|
101-200
|
2:
|
101-200
|
|
3:
|
36-60
|
3:
|
36-60
|
|
3:
|
201-400
|
3:
|
201-400
|
|
|
4:
|
61-90
|
4:
|
61-90
|
|
|
|
|
|
|
|
5:
|
91-125
|
5:
|
91-125
|
|
|
|
|
|
|
|
Over 125, add 1 fixture per restroom for each additional
45 males/females.
See Footnote #1
|
|
Over 400, add 1 fixture per restroom for each additional
200 males/females.
See Footnotes #1 and #6
|
|
|
|
|
|
|
|
|
Drinking Fountains4
(Fixtures per person)
|
1 per 75
|
|
See Footnote #12
|
|
|
|
|
|
|
|
|
Other Fixtures
(Fixtures per person)
|
1 Service Sink per
floor on which restrooms are located
|
|
1 Service Sink and 1 3-Compartment Sink as required by 77
Ill. Adm. Code 750
See Footnote #6
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Back to the
TOP
Type of Building
|
Schools-Student Use:
Elementary
|
Schools-Student
Use:
Secondary, Colleges, Universities, Adult Centers, Etc.
|
|
|
|
|
|
|
|
|
|
Male
|
Female
|
|
Male
|
Female
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Water
Closets
(Fixtures
per person)
|
1:
|
1-20
|
1:
|
1-20
|
|
1 per 40
|
1 per 20
|
|
2:
|
21-50
|
2:
|
21-50
|
|
See Footnote #1
|
|
|
Over 50, add 1 fixture per restroom for each additional 50
persons.
See Footnote #1
|
|
|
|
|
|
|
|
|
|
|
Urinals
(Fixtures per person)
|
See
Footnote #2
|
See Footnote #2
|
|
1 per 40 See Footnote #2
|
See
Footnote #2
|
|
|
|
|
|
|
|
|
Lavatories3
(Fixtures
per person)
|
1:
|
1-25
|
1:
|
1-25
|
|
1 per 40
|
1 per 40
|
|
2:
|
26-50
|
2:
|
26-50
|
|
1 per exercise room
|
|
|
Over 50, add 1 fixture per restroom for each additional 50
persons.
See Footnote #1
|
|
|
|
|
|
|
|
|
Drinking Fountains4
(Fixtures per person)
|
1 per 75
|
|
1 per 75
|
|
|
|
|
|
|
Other Fixtures
(Fixtures per person)
|
1 Service Sink per
floor
|
|
1 Service Sink per
floor
|
|
|
|
|
|
|
|
|
|
|
|
|
Back to the
TOP
|
Type of
Building
|
Day Care, Nursery and Preschool Centers
Toddlers 16-36 Months Excludes Infants
(0-15 Months)
|
|
|
|
|
Male
|
Female
|
|
Water Closets
(Fixtures per person)
|
1:
|
1-10
|
1:
|
1-10
|
|
|
2:
|
11-25
|
2:
|
11-25
|
|
|
|
3:
|
26-50
|
3:
|
26-50
|
|
|
|
4:
|
51-75
|
4:
|
51-75
|
|
|
|
5:
|
76-100
|
5:
|
76-100
|
|
|
|
6:
|
101-125
|
6:
|
101-125
|
|
|
|
7:
|
126-150
|
7:
|
126-150
|
|
|
|
8:
|
151-175
|
8:
|
151-175
|
|
|
|
Over 175: Add a fixture per
restroom for each additional 50 males/females.
See Footnotes #1 and #11
|
|
|
|
|
|
Urinals
(Fixtures per person)
|
See
Footnote #2
|
See
Footnote #2
|
|
|
|
|
|
Lavatories3
(Fixtures per person)
|
1:
|
1-10
|
1:
|
1-10
|
|
|
2:
|
11-25
|
2:
|
11-25
|
|
|
|
3:
|
26-50
|
3:
|
26-50
|
|
|
|
4:
|
51-75
|
4:
|
51-75
|
|
|
|
5:
|
76-100
|
5:
|
76-100
|
|
|
|
6:
|
101-125
|
6:
|
101-125
|
|
|
|
7:
|
126-150
|
7:
|
126-150
|
|
|
|
8:
|
151-175
|
8:
|
151-175
|
|
|
|
Over 175: Add a fixture per
restroom for each additional 50 males/females.
See Footnotes #1 and #11
|
|
|
|
|
|
Drinking Fountains4
(Fixtures per person)
|
1 per 75
|
|
|
|
|
|
Other Fixtures
|
1 Service Sink Per Facility
|
Back to the
TOP
Type of Building
|
Hospital Individual Room
|
Hospitals Ward Room
|
|
|
|
|
|
Water Closets
|
1 per room
|
1 per 8 patients
|
|
(Fixtures per person)
|
|
|
|
|
|
|
|
Urinals
|
None
|
None
|
|
(Fixtures per person)
|
|
|
|
|
|
|
|
Lavatories3
|
1 per room
|
1 per 8 patients
|
|
(Fixtures per person)
|
|
|
|
|
|
|
|
Bathtubs, Showers
|
1 per room
|
1 per 8 patients
|
|
(Fixtures per person)
|
|
|
|
|
|
|
|
Drinking Fountains4
|
None
|
1 per 75
|
|
(Fixtures per person)
|
|
|
|
|
|
|
|
Other Fixtures
|
1 Service Sink
|
1 Service Sink
|
|
(Fixtures per person)
|
per floor
|
per floor
|
|
|
|
|
|
Back to the
TOP
Type of Building
|
Institutional – Other than
Hospitals or Penal Institutions
(on each floor)
|
Penal Institutions
For Prisoner Use
Cell or Dormitories
|
|
|
|
|
|
|
|
Male
|
Female
|
|
|
|
|
|
|
|
Water Closets
|
1 per 25
|
1 per 20
|
1 per cell
|
|
(Fixtures per person)
|
|
|
1 per 8 in a dormitory
|
|
|
|
|
|
|
Urinals
|
1 per 50 (#2)
|
See Footnote #2
|
None
|
|
(Fixtures per person)
|
|
|
|
|
|
|
|
|
|
Lavatories3
|
1 per 10
|
1 per 10
|
1 per cell
|
|
(Fixtures per person)
|
|
|
1 per 8 prisoners in a dormitory
|
|
|
|
|
|
|
|
|
|
|
Bathtubs, Showers
|
1 per 8
|
1 per 8
|
1 per 8 prisoners
|
|
(Fixtures per person)
|
|
|
|
|
|
|
|
|
|
Drinking Fountains4
|
1
per 75
|
1 per 75 prisoners
|
|
(Fixtures per person)
|
|
|
|
|
|
|
|
|
|
Other Fixtures
|
1
Service Sink per floor
|
1 Service Sink per floor
|
|
(Fixtures per person)
|
|
|
|
Back to the TOP
Instructions/Footnotes For Table B
The numbers of fixtures required for employees are included
in the numbers shown in Table B for all building types/uses except Hospital
Rooms, Penal Institutions, and Other Institutions. The entry in Table B
entitled "All Facilities for Employee Use" shall be used to determine
the minimum number of fixtures required for employees in hospitals, penal/other
institutions, and all other buildings/facilities that do not appear in Table B.
Questions concerning the minimum numbers of fixtures
required for building types not listed in Appendix A, Table B, shall be
referred to the Department in writing prior to construction for a decision
concerning the minimum numbers (and types) of plumbing fixtures required.
Footnotes:
1. The
figures shown are the minimum number of fixtures required for the number of
persons indicated or any fraction thereof. Based on the total occupant load
determined, the number of fixtures shall be calculated assuming 50 percent of
the occupants are male and 50percent are female. The total male/female
occupants shall be calculated first; then the number of fixtures for each (males/females)
shall be determined from the appropriate table.
2. Urinals
may be substituted for water closets for males, not to exceed ˝ of the required
total number of water closets. Comparable fixtures for females may be
substituted for water closets for females, not to exceed ˝ of the required
total number of water closets.
3. 18
lineal inches of wash sink or 18 inches of a circular basin, when provided with
water outlets for such space, shall be considered equivalent to one lavatory.
4. Whenever
a drinking fountain is required by this code, bottled drinking water or a water
dispensing faucet (water station) may be substituted for a drinking fountain,
provided drinking water is accessible to the public. When bottled drinking
water is provided in lieu of a drinking fountain, the bottled water used must
be commercially sealed in accordance with the Illinois Bottled Water Act [815
ILCS 310] or must comply with the Department's Public Area Sanitary Practice
Code (77 Ill. Adm. Code 895).
5. The
kitchen sink and laundry tray or connection for the washer are not required for
the hotel/motel unit.
6. In
addition to providing separate handwashing facilities in the kitchen for
employees, all food service establishments shall provide a minimum of one
service/utility sink and one three-compartment sink to sanitize dishes and
eating utensils; however, a mechanical dishwasher may be substituted for a
3-compartment sink to sanitize dishes and utensils. (See 77 Ill. Adm. Code
750.)
7. When
bathtubs/showers are required for employees by OSHA requirements, collective
bargaining agreements, etc., they shall be provided at the rate of one per 10
employees.
8. Food
Service Establishments with no more than 10 combined employees and seats (for
patrons) at any one time need not provide public restrooms, provided the
employee restrooms are accessible and made available to the public.
9. Bed
and Breakfast facilities with more than 5 sleeping rooms shall meet the minimum
requirements of this Part for Hotel/Motel units. Bed and Breakfast facilities
with 5 or fewer sleeping rooms, in conformance with the Bed and Breakfast Act
[50 ILCS 820], need not provide individual restrooms for each sleeping room.
10. Businesses
which sell motor fuel but do not have any employees working as attendants are
not required to provide public restrooms.
11. In
Day Care Centers providing restroom training facilities for occupants ages 3
and younger where continuous adult supervision is provided, restrooms are not
required to be separated into facilities for males and females, and are allowed
to contain multiple lavatories and water closets as required by this Part.
Public restrooms shall be required for everyone over the age of 3 separate from
the restroom training facilities as required by this Part.
12. Drinking
water shall be provided in accordance with Section 890.720(f).
Back to the
TOP
(Source: Amended at 28 Ill.
Reg. 4215, effective February 18, 2004)